GENERAL FEATURES:
Range with 9 box types from 450 until
1250, provided with three-phase 4 and 6 pole
motors 400ºC/2H. Air-flow
from 5.500 m3
/h until 109.000 m3
/h.
Maximum working temperature 60ºC in
continuous.
MANUFACTURING FEATURES:
· BOX : Box manufactured in galvanized
steel sheet with sound and
Thermal proofing. Easy motor access and
fan maintenance through removable
Panels.
· Fan:
· HBFX: Axial fan, circular reinforced
frame. Motor-impeller assembly through
modular system. Cast aluminum impeller
variable pitch angle. Epoxy powder coat
finishing.
ATEX standard asynchronous motor CERTIFIED
400ºC/2H.
Standard voltages 230/400V 50Hz for
three-phase, motors up to 5,5HP and
400/690V 50Hz for higher powers.
APPLICATIONS:
Specially designed for duct and wall
mounting:
· Smoke emergency exhaust fans with the
motor INSIDE THE HAZARDOUS AREA.
· Due to his design inside a cabinet and with
square inlet and outlet of the fan do easy the
installation in rectangular duct systems.
· Flameproof or explosion proof fans with
ATEX certificated motors.
UNDER REQUEST:
· “Implemented” (“B form”) impeller (air sense from
Impeller to motor), 100% reversible impeller.
· 60Hz fans.